Details
Feature | Specification |
---|---|
Sensing Element | Pt1000 (platinum resistance) |
Probe Length | 400 mm (16″) bendable copper/polyolefin |
Temperature Range | –50 °C to +50 °C (–58 °F to +122 °F) |
Operating Voltage | 13.5–35 V DC |
Output Signal | 4–20 mA (loop-powered, 2-wire) |
Accuracy | ±0.9 K (–50…+50 °C) |
Time Constant | ~30 s at air velocity of 2 m/s |
Housing/IP Rating | Plastic enclosure, IP54 |
Power Consumption | < 1 VA |
Dimensions | Housing ~88×80×39 mm, probe 400 mm |
Protection Class | Class III (low voltage) |
View more about SIEMENS DUCT TEMPERATURE SENSOR QAM2171.040 on main site