AUTONICS TK4S-R4RN

AUTONICS TK4S-R4RN

Category: CONTROLLER

Specifications
Details

🔧 Key Specifications

  • Display: 4-digit 7-segment LED

  • Control Methods: ON/OFF, P, PI, PD, PID

  • Input Types:

    • Thermocouples: K, J, E, T, B, R, S, N, C, G, L, U, Platinel II

    • RTD: DPt100Ω, DPt50Ω, JPt100Ω, Cu100Ω, Cu50Ω, Nickel 120Ω

    • Analog: 0–100mV, 0–5V, 1–5V, 0–10V, 0–20mA, 4–20mA

  • Sampling Cycle: 50ms

  • Control Output: Relay (250VAC, 3A)

  • Optional Outputs: Alarm 1, DC 4–20mA transmission

  • Power Supply: 100–240VAC, 50/60Hz

  • Protection Rating: IP65 (front panel)

  • Display Accuracy:

    • RTD/Thermocouple: ±0.3% or ±1°C (whichever is greater) at room temperature (23°C ±5°C); ±0.5% or ±2°C outside room temperature

    • Analog: ±0.3% F.S. ±1 digit at room temperature; ±0.5% F.S. ±1 digit outside room temperature

    • CT Input: ±5% F.S. ±1 digit

  • Hysteresis: Adjustable from 1 to 100°C (0.1 to 100.0°C)

  • Proportional Band: 0.1 to 999.9°C (0.1 to 999.9%)

  • Integral Time: 0 to 9999 seconds

  • Derivative Time: 0 to 9999 seconds

  • Control Period: 0.1 to 120.0 seconds for relay/SSR drive output; 1.0 to 120.0 seconds for current output or SSR drive output

  • Manual Reset: 0.0 to 100.0%

  • Ambient Temperature: Operating: -10 to 50°C; Storage: -20 to 60°C

  • Ambient Humidity: 35 to 85% RH (non-condensing)

  • Insulation Type: Double or reinforced insulation; dielectric strength between measuring input and power part: 2kV

  • Weight: Approximately 150g (unit only)


View more about AUTONICS TK4S-R4RN on main site